Advance Search
Volume 32 Issue S2
Mar.  2025
Turn off MathJax
Article Contents
ZHOU Li, LI Gang, TAO Hai-quan, CAO Bang-wei, PAN Kai. Partial Discharge Test for 1000 MW Nuclear Power Generator[J]. Nuclear Power Engineering, 2011, 32(S2): 58-62.
Citation: ZHOU Li, LI Gang, TAO Hai-quan, CAO Bang-wei, PAN Kai. Partial Discharge Test for 1000 MW Nuclear Power Generator[J]. Nuclear Power Engineering, 2011, 32(S2): 58-62.

Partial Discharge Test for 1000 MW Nuclear Power Generator

  • Received Date: 2011-06-08
  • Rev Recd Date: 2011-08-26
  • Available Online: 2025-03-08
  • Partial discharge test is an effective method for monitoring and preventing winding insulation defects of generator stators.This paper,through the comparison of partial discharge tests on generators for Unit 3 & 4 of Ling’ao Phase II and the generator in DFEM for unit 1 of Hongyanhe Phase I,analyzes and studies the problem of partial discharge value beyond national standard for the first domestic 1000MW nuclear power inner water cooling generators.The cause for the abnormal partial discharge value is found out,and it is concluded that the partial discharge value is an inherent property of this type of generator,which provides a theoretical foundation for the safe operation and partial discharge test evaluation of same models.

     