Abstract:
In order to meet the requirements of the optimization design work for the digital instrument and control system of the nuclear power plant (NPP),the transient simulation program for PWR,CATIA 2 code,has been improved.The main improvements are that the digital sampling module,the digital processing time steps of the Δ
T protection channels and the sample time of the input parameters for the Δ
T protection channels are introduced in the CATIA 2 code.A new over temperature setpoint equation module according to the digital technology is provided.By analyzing and comparing the numerical simulation results,the improvements are proved to be reasonable and feasible.