Advance Search
Volume 26 Issue 3
Jun.  2005
Turn off MathJax
Article Contents
DONG Hua-ping, ZHANG Jian-min. PID Parameters Setting on Level Control System of Steam Generator in Qinshan Phase II NPP[J]. Nuclear Power Engineering, 2005, 26(3): 272-276.
Citation: DONG Hua-ping, ZHANG Jian-min. PID Parameters Setting on Level Control System of Steam Generator in Qinshan Phase II NPP[J]. Nuclear Power Engineering, 2005, 26(3): 272-276.

PID Parameters Setting on Level Control System of Steam Generator in Qinshan Phase II NPP

  • Received Date: 2004-06-08
  • Rev Recd Date: 2004-12-27
  • Publish Date: 2005-06-15
  • Based on SimPort simulation platform of nuclear power plant, a simulation model on the level control system of steam generator in the unit one of Qinshan Phase II NPP was established. Using this model, transient simulation experiments and researches with different conditions were conducted and the setpoints of the level control system were obtained. To level controller, KP, TI and TD are 4.25, 425s and 10s respectively. To flow controller, KP is 1.0 and TI is 13s. These setpoints are in agreement with the actual values and can be referred by engineering technician.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (4) PDF downloads(0) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return