Advance Search
Volume 30 Issue 2
Apr.  2009
Turn off MathJax
Article Contents
LIU Zhi-yong, LIU Mei-qing, JIANG Jing, ZHAO Wen-sheng. Pipe Leak Detection Based on Inverse Transient Analysis[J]. Nuclear Power Engineering, 2009, 30(2): 90-94.
Citation: LIU Zhi-yong, LIU Mei-qing, JIANG Jing, ZHAO Wen-sheng. Pipe Leak Detection Based on Inverse Transient Analysis[J]. Nuclear Power Engineering, 2009, 30(2): 90-94.

Pipe Leak Detection Based on Inverse Transient Analysis

  • Received Date: 2007-12-22
  • Rev Recd Date: 2008-04-01
  • Available Online: 2025-07-28
  • Publish Date: 2009-04-15
  • The pipe leak detection method based on ITA(Inverse Transients Analysis)was studied in this paper.The problem of pipe leak detection was converted to optimization problem.Taking the leak location and leak size as decision variables,the optimization model,in which the object function was to minimize the sum of square difference between calculation and measured value,was established.The GA(Genetic Arith-metic),in which the 1-D approximation Vardy-Brown model was used to calculate fitness value,was applied to solve the optimization model.The feasibility of this method was validated by experiment.Moreover,through analyzing the main influence factors for the method,this paper pointed out that the detection result was impressible to the water hammer wave speed.

     