Advance Search
Volume 43 Issue 6
Dec.  2022
Turn off MathJax
Article Contents
Gao Longjiang, Xu Qiwei, Yu Tianda, Tang Jiankai, Luo Lingyan, Li Qingzhao, Huang Siyu. Research on Proportional Complex Integral Control Strategy for Rod Position Detector Power Supply System[J]. Nuclear Power Engineering, 2022, 43(6): 162-167. doi: 10.13832/j.jnpe.2022.06.0162
Citation: Gao Longjiang, Xu Qiwei, Yu Tianda, Tang Jiankai, Luo Lingyan, Li Qingzhao, Huang Siyu. Research on Proportional Complex Integral Control Strategy for Rod Position Detector Power Supply System[J]. Nuclear Power Engineering, 2022, 43(6): 162-167. doi: 10.13832/j.jnpe.2022.06.0162

Research on Proportional Complex Integral Control Strategy for Rod Position Detector Power Supply System

doi: 10.13832/j.jnpe.2022.06.0162
  • Received Date: 2022-01-11
  • Rev Recd Date: 2022-07-25
  • Publish Date: 2022-12-14
  • Single-phase inverter works in voltage source mode in rod position detection system of nuclear power plant. The load rod position detector is usually equivalent to a inductive load, but inductive load connected to the output of the inverter cannot output a stable sinusoidal voltage. In this paper, a proportional complex integral (PCI) control strategy is proposed for the power supply system of single-phase inverter rod position detector, and the parameter design method of the controller is given. First, based on the frequency domain model of the system, the analytical expressions of the parameters of the current loop proportional integral (PI) controller and the voltage loop PCI controller are derived, and the influence of the load parameters on the system stability is considered. Then, the expected open loop cut-off frequency and phase margin of current loop and voltage loop are set, and the PI and PCI controller parameters are analytically calculated by this method. Finally, through MATLAB simulation, it is verified that the proposed method can obtain stable output voltage and output current of single-phase inverter under inductive load, and the output current total harmonic distortion (THD) is less than 0.3%. This method can provide guidance for the power supply system control of single-phase inverter rod position detector.

     

  • loading
  • [1]
    李国勇,金远,郑杲,等. 落棒时间自动测量方法研究与实现[J]. 核动力工程,2016, 37(4): 53-57.
    [2]
    王春蕾,陈帅君,黄可东,等. 基于根轨迹法的核电厂棒位探测器电源PR控制的研究[J]. 核动力工程,2021, 42(1): 113-117. doi: 10.13832/j.jnpe.2021.01.0113
    [3]
    LI X Q, LIN P F, TANG Y, et al. Stability design of single-loop voltage control with enhanced dynamic for voltage-source converters with a low LC-resonant-frequency[J]. IEEE Transactions on Power Electronics, 2018, 33(11): 9937-9951. doi: 10.1109/TPEL.2018.2794066
    [4]
    KUPERMAN A. Proportional-resonant current controllers design based on desired transient performance[J]. IEEE Transactions on Power Electronics, 2015, 30(10): 5341-5345. doi: 10.1109/TPEL.2015.2408053
    [5]
    许明周,何佳佶,郑杲,等. 基于滞环控制的核电厂棒位探测器电源控制方法分析与设计[J]. 核动力工程,2018, 39(S1): 1-4. doi: 10.13832/j.jnpe.2018.S1.0001
    [6]
    李梦书,李国勇,郑杲,等. 基于前馈控制的棒位探测器励磁电源研究与设计[J]. 核动力工程,2021, 42(1): 177-181.
    [7]
    郭小强,邬伟扬,赵清林,等. 三相并网逆变器比例复数积分电流控制技术[J]. 中国电机工程学报,2009, 29(15): 8-14. doi: 10.3321/j.issn:0258-8013.2009.15.002
    [8]
    郑杲,黄可东,余海涛,等. 基于IGBT的反应堆控制棒驱动机构电源控制装置[J]. 核动力工程,2014, 35(1): 138-141.
    [9]
    丁凯,陈章妍,黄萌,等. 阻感性负载下单相离网逆变器稳定性分析与控制[J]. 电力系统保护与控制,2017, 45(6): 80-86. doi: 10.7667/PSPC160427
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Figures(10)  / Tables(2)

    Article Metrics

    Article views (161) PDF downloads(22) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return