Advance Search
Volume 34 Issue 5
Mar.  2025
Turn off MathJax
Article Contents
YU Ren, KONG Jing-song, XIANG Xin-min, GUO Wei-qun. Research on pH Automatic Adjustment System in Radioactive Decontamination Waste Liquid Evaporation Treatment System[J]. Nuclear Power Engineering, 2013, 34(5): 139-141,153.
Citation: YU Ren, KONG Jing-song, XIANG Xin-min, GUO Wei-qun. Research on pH Automatic Adjustment System in Radioactive Decontamination Waste Liquid Evaporation Treatment System[J]. Nuclear Power Engineering, 2013, 34(5): 139-141,153.

Research on pH Automatic Adjustment System in Radioactive Decontamination Waste Liquid Evaporation Treatment System

  • Received Date: 2012-06-18
  • Rev Recd Date: 2012-07-15
  • Available Online: 2025-03-08
  • During the operation process of the waste liquid evaporation treatment system,the pH value of the radioactive decontamination waste liquid will change constantly,and lead to the violent fluctuation of the liquid level in the evaporator.In the paper,the causes of this phenomenon are analyzed,and the technical solution for this problem which introduces a waste liquid pH value online monitoring and automatic adjustment system into the waste liquid loading pipeline is designed.By adding suitable amount of acid or alkali solution automatically into the loading waste liquid,its pH valve can be stabilized within the given range.

     